| Voltage | 415v |
| Power Rating | 1.5 kW |
| Outlet Size | DN 80 |
| Port-to-Port Length | 360.0 mm |
| Shipping Weight | 125.0 kg |
| Package Dimensions | 100.0 × 60.0 × 80.0 mm |
| Minimum Pressure | 4.8 m head (0.5 bar) |
| Maximum Pressure | 11.8 m head (1.2 bar) |
| Minimum Flow | 4.0 m³/h (1.1 L/s) |
| Maximum Flow | 60.0 m³/h (16.7 L/s) |
This listing is for a Grundfos TPD pump from the TP family of dry-rotor, single-stage in-line circulators. The TPD is the twin-head version, providing duty/standby flexibility or parallel operation using identical in-line suction and discharge ports. It is designed for heating, cooling and industrial circulation duties where serviceability and continuity of operation are important.
The pump uses the top-pull-out design, meaning each power head (motor, pump head and impeller) can be removed for maintenance while the pump housing remains in the pipework.
Condition: supplied as a used pump. The unit shows cosmetic wear consistent with previous service use.
It has been inspected prior to dispatch and confirmed free-turning and operational.
Guarantee: supplied with our 6-month guarantee.
Need help confirming suitability?
Call us on 01803 220416 for technical advice.
Full technical specifications, curves and documentation can be viewed on the official Grundfos product page:
View Grundfos TPD 80-120/2 (99222229) – Variant details
Seal operating temperature (BQBE): typically suitable from 0 °C up to 120 °C in water duties (EPDM-limited).
BQBE combines a silicon-carbide primary face with a carbon-impregnated counterface. This pairing offers very good corrosion resistance and smooth, low-friction running in clean heating and cooling water, while the silicon-carbide face provides improved wear resistance compared with softer materials. It is a practical and widely used seal choice for normal HVAC circulation duties.
Air-conditioning note: BQBE is suitable for chilled-water systems operating above 0 °C. It is not suitable for sub-zero brine/glycol circuits, ice-storage systems, or refrigerants where liquid temperature may fall below 0 °C.
Yes – the TPD twin configuration allows duty/standby or parallel operation, but this requires an external control system. Automatic changeover and alternation are not managed by the pump itself; they must be provided by a separate control panel, inverter drive system, or BMS controller configured for twin-pump operation.
This model uses DN80 PN10 DIN flanges with a port-to-port length of 360 mm. Where dimensions match, it can replace other DN80 in-line circulators from manufacturers such as Wilo, Lowara and KSB, subject to hydraulic duty and system requirements.
Yes – each head uses a top-pull-out design, so the power head can be removed while the pump housing remains installed in the pipework.
Stock code: #2984
We specialise in supplying quality pumps and equipment. This unit is supplied as used, inspected prior to dispatch and supplied with a 6-month guarantee.
Specification & guidance notice: Technical information and FAQ content are provided in good faith based on manufacturer literature and industry experience. Descriptions of hydraulic types and application suitability represent general guidance only and do not constitute a guarantee of performance. Actual results will depend on system design, pipework losses, media characteristics, and installation conditions. Please consult the manufacturer & thier documentation and satisfy yourself that the equipment is suitable for your specific application prior to purchase.